This standard specifies the technical requirements, test conditions, test items, test requirements, test procedures and test report contents for the voltage fault ride through capability of wind turbine generator units (hereinafter referred to as wind turbines).
This standard is applicable to the grid-connected wind turbines.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
JJF 1059.1 Evaluation and expression of uncertainty in measurement
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
low voltage ride through capability of wind turbine
capability of the wind turbine that can ensure no disconnection and continuous operation within a certain voltage dip range and time interval in case of voltage dip caused by grid fault or disturbance
3.2
high voltage ride through capability of wind turbine
capability of the wind turbine that can ensure no disconnection and continuous operation within a certain voltage swell range and time interval in case of voltage swell caused by grid fault or disturbance
GB/T 36995-2018 The following standards are cited: